Guide article of the new Toolkit3 app to allow users to configure the targets transmitted to the remote/external equipment (charger/inverter).
Navigate to the screen via the Menu and choose the Configuration tab. Choose Remote Control from the drop-down menu.
Values are available once you have selected template Ramped Targets and have enabled limited charge and discharge on their respective screens.
Beyond the software version 2.17.9, this has been enhanced to ramp down the targets when full or empty, to be more gentle on the batteries to avoid the balancing overshoot.
The ramp-down targets for both charging and discharge are available for inverters that accept the CANbus profile:
Editing is only available when in 'Technician' mode.
For guide on how to make changes, go to Configuration Guide and Icons.
High / Limited (Original) | |
High / Limited (Advanced) | |
Ramped Targets |
Current state from the charging control logic (Off, Limited Power, High Power)
Voltage (High) | Target voltage setting to be sent to the external system when in a high power/normal charging state. |
Current (High) | Target current setting to be sent to the external system when in a high power/normal charging state. |
SoC% (High) | Target power (VA) setting to be sent to the external system when in a high power/normal charging state. |
Voltage (Limited) | Target voltage setting to be sent to the external system when in a low/limited power charging state. |
Current (Limited) | Target current setting to be sent to the external system when in low/limited power charging state |
SoC% (Limited) | Target power (VA) setting to be sent to the external system when in a low/limited charging state. |
Voltage (Scaling) |
Voltage values are stored as an unsigned int16 with values of 1, 10, or 100, these are used to scale the decimal places. When selecting the appropriate communication integration these values are remapped if required. If this field is not visible, then change the template to Advanced, adjust and save. And then return to the original desired template. When a CANbus profile is changed, and when you press the default mode on the screen, it will adjust this value to suit the equipment. |
Current (Scaling) |
Current (Amp) are stored as an unsigned int16 with values of 1, 10, or 100, these are used to scale the decimal places. When selecting the appropriate communication integration these values are remapped if required. If this field is not visible, then change the template to Advanced, adjust and save. And then return to the original desired template. When a CANbus profile is changed, and when you press the default mode on the screen, it will adjust this value to suit the equipment. |
SoC% (Scaling) |
Power (VA) is stored as an unsigned int16 with values of 1, 10, or 100, these are used to scale the decimal places. When selecting the appropriate communication integration these values are remapped if required. If this field is not visible, then change the template to Advanced, adjust and save. And then return to the original desired template. When a CANbus profile is changed, and when you press the default mode on the screen, it will adjust this value to suit the equipment. |
Current state from the discharging control logic (Off, Limited Power, High Power)
Voltage (High) | Target voltage setting to be sent to the external system when in a high power / normal discharging state. |
Current (High) | Target current setting to be sent to the external system when in a high power / normal discharging state. |
SoC% (High) | Target power (VA) setting to be sent to the external system when in a high power / normal discharging state. |
Voltage (Limited) | Target voltage setting to be sent to the external system when in a low/limited power discharging state. |
Current (Limited) | Target current setting to be sent to the external system when in a low/limited power discharging state. |
SoC% (Limited) | Target power (VA) setting to be sent to the external system when in a low/limited power discharging state. |
Voltage (Limited) | Voltage values are stored as an unsigned int16 with values from 0 to 65535, these are scaled to adjust for the decimal point. When selecting the appropriate communication integration these values are remapped if required. |
Current (Limited) | Currents (amps) values are stored as an unsigned int16 with values from 0 to 65535, these are scaled to adjust for the decimal point. When selecting the appropriate communication integration these values are remapped if required. |
SoC% (Limited) | Power (VA) values are stored as an unsigned int16 with values from 0 to 65535, these are scaled to adjust for the decimal point. When selecting the appropriate communication integration these values are remapped if required. |
Ticks Tx/Rx | Flashes as status telemetry is received |
Unk |
Actual | Target | |
Flags | Current values received from the external remote system (if available). | |
Timestamp | Time when information was received from the external system. | |
Voltage |
Value received from the external remote system (if available). If the value shown is zero (0) or NS (Not Supplied) or NA (Not Applicable), this means this value has not been sent to the BMS. This does not mean there is an issue. This field is optional in the protocol and only a select few manufacturers or only some of their products have this functionality. |
Target voltage transmitted to the external remote system. |
Current |
Value received from the external remote system (if available). If the value shown is zero (0) or NS (Not Supplied) or NA (Not Applicable), this means this value has not been sent to the BMS. This does not mean there is an issue. This field is optional in the protocol and only a select few manufacturers or only some of their products have this functionality. |
Target current value transmitted to the external remote system. |
Power |
Value received from the external remote system (if available). If the value shown is zero (0) or NS (Not Supplied) or NA (Not Applicable), this means this value has not been sent to the BMS. This does not mean there is an issue. This field is optional in the protocol and only a select few manufacturers or only some of their products have this functionality. |
Target power value transmitted to the external remote system. |
Temperature | Actual temperature received from the external remote system (if available). | Target temperaturetemperature received from the external remote system (if available). |
Actual | Target | |
Flags | Current values received from the external remote system (if available). | |
Timestamp | Time when information was received from the external system. | |
Voltage | Value received from the external remote system (if available). | Target voltage transmitted to the external remote system. |
Current | Value received from the external remote system (if available). | Target current value transmitted to the external remote system. |
Power | Value received from the external remote system (if available). | Target power value transmitted to the external remote system. |
Temperature | Actual temperature received from the external remote system (if available). | Target emperature received from the external remote system (if available). |