Administrative screen for the WatchMon supervisor hardware providing a summary, and how to understand and see the various fields available to configure the Voltage aspect of control logic.
This screen is accessed via the Control Logic option on the Menu, then choosing the VoltView tab. Editing only available when in Technician mode.
Values read from device.
Cell voltage threshold that is OK to operate, if above will change state when monitoring is enabled, output is connected to the Critical Contactor.
Cell voltage alert when above will flash RED led on CellMon.
Cell voltage threshold to charge up to, if above will stop when enabled to monitor.
Bypass Cell Voltage, when above will bypass/bleed power from the cell.
Cell voltage to resume / recover the charging process once the actuals have dropped below the threshold specified.
Nominal Cell Voltage for battery chemistry, info only.
Cell voltage that when below will put the system is into limited power mode, hence remove non critical loads or run in limp mode for discharge, only available with Limited power enabled.
Cell voltage that when below will hold the charging process in limited power state until the system recharges above this threshold.
Cell voltage that if above will resume / restart the discharging process state, when monitoring is enabled.
Cell voltage that if below will stop the discharging process state, when monitoring is enabled.
Cell voltage alert when below will flash RED led on CellMon.
Cell voltage threshold that is OK to operate, if below will change state when monitoring is enabled, output is connected to the Critical Contactor.
Values read from device.
WatchMon supply voltage threshold that is OK to operate, if above will change state when monitoring is enabled, output is connected to the Critical Contactor.
WatchMon supply voltage threshold that is OK to operate, if above will stop charging when monitoring is enabled.
The shunt State of charge (SoC%) threshold to resume / recover the charging process once the cells have dropped to the threshold specified.
WatchMon supply voltage that if above will resume / restart the discharging process state, when monitoring is enabled.
WatchMon supply voltage that if below will stop the discharging process state, when monitoring is enabled.
WatchMon supply voltage threshold that is OK to operate, if below will change state when monitoring is enabled, output is connected to the Critical Contactor.
Values read from device.
Shunt voltage threshold that is OK to operate, if above will change state when monitoring is enabled, output is connected to the Critical Contactor.
The shunt voltage threshold to charge up to, if above will stop when enabled to monitor.
The shunt voltage threshold to resume / recover the charging process once the actuals have dropped below the threshold specified.
Shunt voltage threshold that is OK to operate when the current is idle (battery at rest), if below will change state when monitoring is enabled, output is connected to the Critical Contactor.
Shunt voltage that when below will put the system is into limited power mode, hence remove non critical loads or run in limp mode for discharge, only available with limited power enabled.
The shunt voltage that when below will hold the charging process in limited power state until the system recharges above this threshold.
Shunt voltage that if above will resume / restart the discharging process state, when monitoring is enabled.
Shunt voltage that if below will stop the discharging process state, when monitoring is enabled.
Shunt voltage threshold that is OK to operate, if below will change state when monitoring is enabled, output is connected to the Critical Contactor. This value is both when idle and under discharge/charge currents.
Pressing this button calls up the knowledge base on this screen.
If figures shown on this page need changing, please go to the following links to change the designated items:
Hardware CellMon: CV2, CV7, CV9, CV11
Control Logic - Critical Battery OK: CV1, CV12, BS1, BS6, QV1, QV6, QV9
Control Logic - Charging Settings: CV5, CV8, CV10, BS4, BS5, QV4, QV7, QV8
Control Logic - Discharging Settings: CV3, CV4, CV6, BS2, BS3, QV2, QV3, QV5